Pipeline centrifugal mounting technique is to determine the critical water pump installation height (i.e., suction). This height refers to the vertical distance from the water surface of the water source to the center line of the pump impeller. It can not be confused with the allowable vacuum height. The allowable vacuum height indicated on the pump manual or nameplate means the vacuum value on the water inlet section of the water pump, Is measured at 1 standard atmospheric pressure, the water temperature of 20 degrees Celsius, the test and measured. It does not consider the condition of the water flow after the water supply pipe is matched. The pump installation height should be allowed to suck vacuum height deducted after the head of the suction pipe loss, the remaining part of the value, it is necessary to overcome the actual terrain water absorption height. Pump installation height can not exceed the calculated value, otherwise, the pump will not pump water. In addition, the impact of the calculated value is the size of the suction pipe lift loss lift, it is appropriate to use the shortest pipe layout, and try to install less elbow and other accessories, but also consider the appropriate with some larger diameter pipes to reduce the flow rate within the pipe.
It should be noted that the pipelines centrifugal pump installation site elevations and water temperature is different from the test conditions, such as the local elevation of 300 meters above or pumping water temperature exceeds 20 degrees Celsius, the calculated value to be amended. Ie atmospheric pressure at different elevations and saturated vapor pressure above 20 degrees Celsius. However, when the water temperature is below 20 degrees Celsius, the saturated steam pressure is negligible.
From the pipe installation technology, the suction pipe requires strict sealing, can not leak, leakage, otherwise it will undermine the pump inlet of the vacuum, so that the water pump to reduce the amount of water is not even pumping in serious cases. Therefore, we should conscientiously do the work of the interface of the pipeline to ensure the construction quality of pipeline connection.
Second, the installation of centrifugal pump height Hg Allowable vacuum suction height Hs refers to the pressure at the pump entrance p1 allows the maximum degree of vacuum.
The actual allowable suction height, Hs, is not a value calculated according to the equation, but a value determined experimentally by the pump manufacturer, which is attached to the pump sample for user investigation. It should be noted that the value of Hs given in the pump sample is the value of water used as working medium, operating conditions of 20 ℃ and pressure of 1.013 × 105Pa, when the operating conditions and working medium are different, need to be converted.
(1) to transport clean water, but the operating conditions and experimental conditions are different, according to the following conversion Hs1 = Hs + (Ha-10.33) - (HÏ…-0.24)
(2) Transfer other liquids When the conditions of liquid and villain are different from the experimental conditions, two-step conversion is required: the first step will be Hs1 detected in the pump sample according to the above formula; the second step will be Hs1 Converted into Hs
2 NPSH Δh
For the oil pump, the calculation of the installation height is calculated using the cavitation allowance Δh, that is, the degree of vacuum that the pump allows to suction the liquid, that is, the allowable installation height of the pump, in meters. Naphthenic residual amount Δh by the pump in the sample, its value is also measured with 20 ℃ water. If you transfer other liquids, also need to be corrected, detailed investigation of the books.
Stroke = standard atmospheric pressure (10.33 meters) - NPSH - safe amount (0.5 meters)
Standard atmospheric pressure pipeline pressure can be 10.33 meters in height.
For example: a pump required NPSH is 4.0 meters, suction Δh?
Solution: Δh = 10.33-4.0-0.5 = 5.83 meters
From a safety point of view, the actual installed pump height should be less than the calculated value. When the calculated value of Hg is negative, it indicates that the suction port of the pump should be below the level of the tank.
Example 2-3 A centrifugal pump from the sample was allowed to suction on the vacuum height Hs = 5.7m. It is known that the total resistance of the suction line is 1.5 mH2O and the local atmospheric pressure is 9.81 × 10 4 Pa. The dynamic head of liquid in the suction line is negligible. Try to calculate
(1) pump installation at 20 ℃ water delivery;
(2) Change the pump installation height to 80 ° C.
Solution: (1) The pump installation height is known when delivering 20 ℃ water: Hs = 5.7m
Hf0-1 = 1.5m
u12 / 2g≈0
The local atmospheric pressure is 9.81 × 104Pa, basically in line with the experimental conditions of the pump factory, so the installation height of the pump Hg = 5.7-0-1.5 = 4.2m.
(2) The installation height of pump when conveying 80 ℃ water
When transporting 80 ℃ water, it can not directly use the Hs value in the pump sample to calculate the installation height. Hs1 = Hs + (Ha-10.33) - (Hυ-0.24)
Ha = 9.81 × 104Pa ~ 10mH2O is known, the saturation vapor pressure of water at 80 ℃ is 47.4kPa.
Hv = 47.4 × 103 Pa = 4.83 mH2O
Hs1 = 5.7 + 10-10.33-4.83 + 0.24 = 0.78m
Hs1 value into the type to obtain the installation height Hg = Hs1-Hf0-1 = 0.78-1.5 = -0.72m
Hg is negative, indicating that the pump should be installed below the tank level, at least 0.72 m below the liquid level.
We are manufacturer of Mini Cement Bolted Silo in China, if you want to buy Cement Bolted Silo,50 Ton Cement Silo,50T Concrete Cement Silo please contact us.chip-mounted cement silo is specially designed and developed for the difficulty of packing and the high transportation cost. The top of the warehouse is equipped with a pressure relief valve to balance the pressure inside the chamber. Prevent explosions. Each cement silo is provided with an upper and lower material level indicator, which can display the empty state of the silo.