Explicit high-current generator usage precautions:
1. At least two people are involved in the test. One person operates and one person supervises operations to ensure safety.
2. The housing must be grounded. Do not neglect safety precautions to prevent personal injury due to low voltage.
3. Proper conductor secondary to the test object conductor should not be too long, the cross-sectional area should be sufficient (current density can be considered 6-8A/mm) contact surface to be clean (a fine gauze can be used to light), otherwise the connector heat, or even The current rises less than the rated value.
4. Before working, check that the power supply has enough capacity, or the power cord is hot and the voltage is lowered and affect normal operation.
5. The work site should not have flammable materials. Temperature rise test should prepare enough fire extinguishing equipment.
6. Continuity (heating) test, on-site personnel should be on duty. And regularly check the source of rising equipment, wires, joints, fever, make a good record. Due to changes in the grid voltage, attention is paid to adjusting TD in order to maintain the rated test current.
7. The test work shall comply with the relevant provisions of the electrical safety work regulations and formulate practical safety measures.
Digital display large current generator technical parameters:
model
TSLQ
Rated Capacity
(KVA)
Riser
Rated input
Riser
Rated output
Impedance voltage
No-load current
Phase current error
<
structure type
Regulator
Riser
Current A
Voltage V
Current A
Voltage V
9/1000
9
9
12
380
1,000
5
<8
<6
0.1
One body/split body
20/2000
20
20
26.8
380
2000
5
<8
<6
0.1
Split
35/4000
35
35
46.9
380
4000
5
<8
<6
0.1
Split
45/5000
45
45
60
380
5000
5
<8
<6
0.1
Split
100/10000
100
100
135
380
10000
5
<8
<6
0.1
Split